IOMM
WARNING

RISK OF FIRE

Use VAC input (indicated above) only on circuits with
a branch circuit protection in accordance with the NEC NFPA
70 to reduce the risk of fire.
These circuits (maximum CB size) also are to be consistent
with the supply current (input amps) indicated in section 3
for the respective number (2–5) and voltage (48 V or 80 V)
of fitted modules and cabinet size (3 or 5 bays).
Ensure that the AC wiring (minimum AC input wire size
[AWG]), indicated in section 3, meet NEC requirements.
Refer to section 3 also for AC input voltage specifications.
Remove the six M6 screws on the top panel of the
charger (Figure 14), with a TORX TX30, and then
remove the panel.

Figure 14 Six M6 Panel crews, Top-panel View

Webasto Charging Systems, Inc.
ProCore Edge North America
VAC Input
Three-phase 480-volt AC
Page 17 of 69 31241-03-0202