LG PQDSBC1 Manual De Instrucciones página 16

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Setting and using method
5) Compressor stop mode
CONTROL
MODE SWITCH
B
Ú Compressor stop mode: The compressor is stopped during cool/heat operation.
6) Operating mode selection mode
CONTROL
MODE SWITCH
C
D
Ú Power save mode: Adjust the set temperature to +3℃(6℉) for cooling and -3℃(6℉) for heating.
CONTROL
MODE SWITCH
E
Ú When setting E mode, turn on 2nd switch of SETTING.
16 Dry contact For Economizer
Input A
Input B
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Input A
Input B
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Input A
Input B
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Indoor unit operating (Compressor in stop mode), locked
Indoor unit prior operating condition maintained
(Compressor not in stop mode), unlocked
Indoor unit stopped, locked
Indoor unit stopped, locked
Indoor unit stopped, unlocked
Indoor unit in cool/high operation, unlocked
Indoor unit in heat/high operation, unlocked
Indoor unit in fan/high operation, unlocked
Indoor unit stopped, locked
Indoor unit in cool/high operation, locked
Indoor unit in heat/high operation, locked
Indoor unit in fan/high operation, locked
Indoor unit prior operating condition maintained, occupied, unlocked
Indoor unit operating with thermal off in cooling mode, occupied, unlocked
Indoor unit prior operating condition maintained, unoccupied, unlocked
Indoor unit prior operating with thermal off in cooling mode, unoccupied, unlocked
Operating mode
Operating mode
Operating mode
Tabla de contenido
loading

Tabla de contenido