Setting and using method
2) General mode
CONTROL
MODE SWITCH
1
2
3
4
5
6
14 Dry contact For Economizer
Input A
Input B
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Operating mode
Indoor unit stopped, locked
Indoor unit prior operating condition maintained, unlocked
Indoor unit stopped, locked
Indoor unit stopped, locked
Indoor unit stopped, locked
Indoor unit operating, unlocked
Indoor unit stopped, locked
Indoor unit stopped, locked
Indoor unit stopped, locked
Indoor unit stopped, locked
Indoor unit prior operating condition maintained, unlocked
Indoor unit operating, unlocked
Indoor unit stopped, locked
Indoor unit stopped, locked
Indoor unit prior operating condition maintained, unlocked
Indoor unit prior operating condition maintained, unlocked
Indoor unit prior operating condition maintained, locked
Indoor unit prior operating condition maintained, locked
Indoor unit prior operating condition maintained, locked
Indoor unit prior operating condition maintained, unlocked
Indoor unit prior operating condition maintained, locked
Indoor unit prior operating condition maintained, locked
Indoor unit prior operating condition maintained, locked
Indoor unit operating, unlocked