2.4 LED Indications

LED off
LED flashes
LED illuminated
Inverter
inverter
charger
alarm
inverter
charger
alarm
inverter
charger
alarm
on
The inverter is switched on and supplies
power to the load. Battery operation.
off
charger only
The inverter is switched on and supplies
on
power to the load.
Pre alarm: overload, or
off
battery voltage low, or
inverter temperature high
charger only
The inverter is switched off.
Alarm: overload, or
on
battery voltage low, or
off
inverter temperature hig, or
DC ripple voltage on battery
charger only
terminal was too high.