Haier HSU09VHG(DB)-W Manual De Instalación
Ocultar thumbs Ver también para HSU09VHG(DB)-W:
Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

Installation Manual of Room Air Conditioner
Preparation
Necessary Tools for Installation
Hammer
Nipper
Hacksaw
Hole core drill
Spanner(17,19 and 26mm)
Gas leakage detector or
soap-and-water solution
Power Source
All wiring to the unit must be in accordance with the National Electric code
and local ordinances.
Drawing for the installation of indoor and outdoor units
The models adopt HFC free refrigerant R410A
more than 5cm
(1 15/16 inches)
more than
10cm
(3 15/16
inches)
Arrangement of piping
directions
Rear left
Rear
Left
right
Right
Below
more than 10cm
The marks from
to
A
in the figure are the
G
name of the parts.
The distance between
the indoor unit and the
floor should be more
than 2m or 6 feet.
more than 60cm
(23 5/8 inches)
The above picture is for reference only. Your product may look different.
Read this manual before installation
Explain the operation of the unit to the user according to this manual
NO.0010538926
Torque wrench
(17mm,22mm,26mm)
Pipe cutter
Flaring tool
Knife
Measuring tape
Reamer
the pitch of drain hose
more than 10cm
(3 15/16 inches)
more than 10cm
(3 15/16 inches)
(3 15/16 inches)
Selection of Installation Place
Indoor Unit - Select a location that is
Robust not causing vibration, where the unit can be supported s ufficiently.
Not affected by heat or steam generated in the vicinity, and where the inlet and outlet of
the unit are not disturbed.
Possible to drain easily, and where piping can be connected with the outdoor unit.
Where conditioned air can be spread in a room evenly.
Place where the distance of more than lm from televisions, radios, wireless apparatuses
and fluorescent lamps 3 feet or approximately.
In the case of fixing the remote controller on a wall, place where the indoor unit can
receive signals when the fluorescent lamps in the room are in use.
Outdoor Unit - Select a location that is
Less affected by rain or direct sunlight and is sufficiently ventilated.
Strong enough to bear the unit, where vibration and noise are not increased.
Not causing a nuisance to neighbors due to discharged air or noise.
Q
A distance marked
is available as illustrated in the below figure.
Attention must be paid to
G
F
A
C
D
E
more than15cm
(5 7/8 inches)
Optional parts for piping
Non-adhesive tape
A
Adhesive tape
B
Saddle (L.S) with screws
C
Connecting electric cable
D
for indoor and outdoor
E
Drain hose
F
Insulating material
G
Piping hole cover
Floor fixing dimensions of the outdoor unit
(Unit:mm / inch)
X
Y
Dimensions(mm/inches)
Model
x
y
140
500
HSU09VHG(DB)-W
(5 1/2)
(19 2/3)
140
500
HSU12VHG(DB)-W
(5 1/2)
(19 2/3)
113.5
583
HSU18VHG(DB)-W
(4 1/2)
(23)
113.5
633
HSU24VHG(DB)-W
(4 1/2)
(24 7/8)
Fixing of outdoor unit
Fix the unit to concrete or block with bolts
(10mm) securely.
When fitting the unit to wall surface, roof or
rooftop, fix the unit securely in consideration
of earthquake and strong wind.
If vibration may affect the house, fix the unit
by attaching a vibration-proof mat.
Z
X
z
256
(10 1/16)
256
(10 1/16)
319.5
(12 5/8)
340
(13 1/2)
Tabla de contenido
loading

Resumen de contenidos para Haier HSU09VHG(DB)-W

  • Página 5: Preparación

    10cm (3 15/16 pulgadas) Izquierda trasera Izquierda Derecha trasera Derecha Inferior Dimensiones(mm/pulgadas) Modelo HSU09VHG(DB)-W (5 1/2) (10 1/16) (19 2/3) más de 10cm más de 10cm (3 15/16 pulgadas) HSU12VHG(DB)-W (3 15/16 pulgadas) (5 1/2) (19 2/3) (10 1/16) 113.5...
  • Página 6: Unidad Interior

    Incline hacia abajo para drenaje Modelo Tubo de líquido (Ø) Tubo de gas (Ø) 09k/12k : B= 60mm(2 3/8 pulgadas ØBmm HSU09VHG(DB)-W 9.52mm (3/8 ") 6.35mm (1/4 ") 18k/24k : B=70mm(2 3/4 pulgadas HSU12VHG(DB)-W 9.52mm (3/8 ") 6.35mm (1/4 ")
  • Página 7: Unidad Exterior

    Unidad exterior 32ft / 10m (09k / 12k) alimentación 50ft / 15m (18k / 24k) Filtro de aceite HSU09VHG(DB)-W En caso de que la elevación A sea superior a 15ft / 5 m, el filtro de HSU12VHG(DB)-W Unidad interior aceite debe instalarse cada 5 ~7 m.
  • Página 8: Etiqueta De Carga De Refrigerante

    Herramienta de 2. Abra la espita inferior del colector y accione la bomba de vacío. Si el indicador de Herramienta de conicidad convencional conicidad para R410A la escala (inferior) alcanza la condición de vacío por un momento, compruebe de nuevo el punto 1. De tipo acoplamiento De tipo palometa De tipo acoplamiento...

Este manual también es adecuado para:

Hsu12vhg(db)-wHsu18vhg(db)-wHsu24vhg(db)-w

Tabla de contenido