Kidde Excellence Serie Hoja De Instalación
Ocultar thumbs Ver también para Excellence Serie:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 6

Enlaces rápidos

Excellence Series Intelligent Addressable Dual
Optical Detector Installation Sheet
EN DE ES FR
IT
NL PL PT SV
1
EN: Installation Sheet
Figures
Figure 1: Locking tab and status LED
(1) Locking tab
(2) Status LED
Figure 2: Inserting the detector head into the mounting base
Description
This installation sheet includes information on the 3000 Series
Intelligent Addressable Dual Optical Detectors shown in the
table below.
Model
Device type
KE-DP3120W
ODni
KE-DP3020W
ODn
The detectors use an advanced optical sensing chamber to
detect smoke.
Using dual optical wavelengths combined with multiple
detection angles, the detectors determine whether to signal a
fire alarm condition by analysing the data from the sensing
chamber to discriminate between fire and non-fire sources.
© 2023 Carrier. All rights reserved.
Description
Intelligent addressable dual
optical detector with integrated
short circuit isolator (white)
Intelligent addressable dual
optical detector (white)
2
All 3000 Series detectors support the Kidde Excellence
protocol and are compatible for use with 2X-A Series fire alarm
control panels with firmware version 5.0 or later. The detectors
are backwards compatible with 2000 Series devices.
Installation
WARNING:
Electrocution hazard. To avoid personal injury or
death from electrocution, remove all sources of power and
allow stored energy to discharge before installing or removing
equipment.
Caution:
For general guidelines on system planning, design,
installation, commissioning, use and maintenance, refer to the
EN 54-14 standard and local regulations.
Install and wire the mounting base, as described in the
installation sheet supplied with the base.
Installing the detector head
Insert the detector head into the mounting base and rotate it
clockwise until it snaps into the locked position (see Figure 2).
The detector may be locked into the mounting base if required.
To do this, remove the locking tab before installation (see
Figure 1).
To remove a locked detector:
1.
Insert a small screwdriver into the locking tab slot
(Figure 1).
2.
Press and rotate the detector anticlockwise.
1 / 23
P/N 3102984-ML • REV 001 • ISS 29NOV23

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Kidde Excellence Serie

  • Página 6: Instalación

    Kontaktinformationen und Todos los detectores de la serie 3000 admiten el protocolo Kidde Excellence y son compatibles para su uso con centrales Produktdokumentationen de alarma contra incendios de la serie 2X-A con la versión de firmware 5.0 o posterior. Los detectores son compatibles con Kontaktinformationen und aktuelle Produktdokumentationen los dispositivos de la serie 2000.
  • Página 7: Estado Del Dispositivo

    Estado del dispositivo Mantenimiento y pruebas El estado del dispositivo se indica mediante el LED de estado Mantenimiento y limpieza (Figura 1, elemento 2), como se muestra en la siguiente tabla. El mantenimiento básico consiste en una inspección anual. No Estado Indicación modifique el circuito interno ni la disposición de los cables.
  • Página 8: Especificaciones Mecánicas Y Del Entorno

    Número de aisladores por lazo Máx. 128 2012/19/UE (directiva WEEE): aquellos productos que tengan este símbolo no Número de dispositivo entre Máx. 32 podrán desecharse como residuos aisladores municipales no clasificados en lo que respecta al ámbito de la Unión Europea. [1] Equivalente a 500 m de cable de 1,5 mm (16 AWG).

Este manual también es adecuado para:

Excellence ke-dp3120wExcellence ke-dp3020w

Tabla de contenido