ds3-ds4: Setting charge voltages
Absorption
ds3-ds4
Voltage
dS3=off
dS4=off
14.4
(default)
dS3=on
14.1
dS4=off
dS3=off
14.7
dS4=on
dS3=on
15.0
dS4=on
Batteries with high antimony content can typically be charged with a lower absorption voltage than
batteries with low antimony content. (Please refer to our book 'Electricity on Board' downloadable
from our website www.victronenergy.com for details and suggestions about charging batteries).
Contact your battery supplier for the correct charge voltages and change (with VE-configure) the
voltage settings if required.
The default charge current setting is 75% of the maximum charge current. This current will be too
high for most applications.
For most battery types the optimal charge current is 0.1-0.2x the battery capacity.
ds5: Inverter frequency
ds6: Search Mode
ds7: AC input current limit
Store the settings by moving DIP switch 8 to 'on' and back to 'off'.
Float
Storage
Voltage
Voltage
13.8
13.2
13.8
13.2
13.8
13.2
13.8
13.2
off = 50Hz on = 60Hz
off = off
off = 12 Amp
Absorption
Time
Suitable for
(hours)
Gel Victron Deep
Discharge
8
Gel Exide A200
AGM Victron Deep
Discharge
Gel Victron Long Life
(OPzV)
8
Gel Exide A600
(OPzV)
Gel MK battery
AGM Victron Deep
Discharge
Tubular plate or
5
OPzS batteries in
semi-float mode
AGM spiral cell
Tubular plate or
6
OPzS batteries in
cyclic mode
on = on
on = 4 Amp
21