KemiDose | pH · ORP · Chlorine
§
§
§
§
§
§
§
§
§
§
§
§
Note: Timeout setting menu, after 120 seconds without action the controller escape itself without saving parameters.
View Parameters
Free Chlorine Measure
Alarms:
Lev CL
OFA CL
Temperature or Totalizer
Flowrate measure,
Moreover,
Alarms sharing messages
• Circ. Pump OFF
• Flow (Reed OFF)
• WiFi OFF
• Remote standby deletes
all the measures
Calibration Menu:
Press
(3 seconds) and calibrate probe pH, Chlorine, Temperature, ORP
0000139024
Dosing Type pH: Proportional, OFF, On/OFF
Dosing Type ORP: Proportional, OFF, On/OFF
•
Note: The ORP dosing is disabled if Dosing type chlorine is different than OFF
Dosing Type Chlorine: Proportional, OFF, On/OFF
Max Flow Rate pumps: 100% (default: 100% [160 strokes/min], range:10-100%)
Aux Relay
•
Aux1 Relay: pH, Disable
•
Aux2 Relay: Chlorine, ORP, Disable
Note: Aux1 and Aux2 relays dose with ON/OFF method
o
Password: 0000 (Note: password disabled, set a value other than: 0000)
Reset Calibration (Note: select the measure to reset: pH; Chlorine; ORP)
Reset All Parameters
PROG Control Panel: displays the electrical signals
Reed (display error, when red): NO/NC
Power ON Delay: Disables the dosing pumps for the set time
Flow Delay: Disables the dosing pumps for the set time
1.4ppm
25°C
rev. 1.0
7.4pH
720mV
EN
pH measure
Alarms:
Lev pH
OFA pH
ORP Measure
Alarms:
Lev CL(ORP)
OFA ORP
6