Instruction Bulletin
Wiser™ Thermostat Remote Temperature Sensor
Model EER57200
Retain for future use.
Description
Safety Precautions
Installation
© 2011 Schneider Electric All Rights Reserved
The EER57200 is a surface mount temperature sensor for use with Wiser
Programmable Communicating Thermostats, models EER56000 and
EER56100. The sensor can be:
Connected to a Wiser thermostat to monitor the temperature of a remote
location
Combined with an onboard temperature sensor to average the
temperature of two locations
Used to monitor the outdoor temperature
The remote temperature sensor is required for Wiser thermostats used in dual
fuel heat pump installations.
This section contains important safety precautions that must be followed before
attempting to install, maintain, or troubleshoot electrical equipment. Carefully
read and follow the safety precautions below.
HAZARD OF ELECTRIC SHOCK
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E.
• This equipment must be installed and serviced by qualified electrical
personnel.
• Turn off all electrical power supplying this equipment before working on
or inside the equipment.
• Always use a properly rated voltage sensing device to confirm that
power is off.
• Replace all devices, doors, and covers before turning on power to this
equipment.
Failure to follow these instructions will result in death or serious
injury.
1. Install the thermostat base and connect it to the HVAC equipment.
Consult the HVAC manufacturer's instructions and the thermostat
Installer's Guide.
2. Connect the thermostat to the base and confirm that the thermostat
operates correctly.
3. Disconnect the thermostat from the base.
4. Run a twisted pair, shielded cable from the remote thermostat to the
mounting location of the temperature sensor. Follow these guidelines or
product performance may be degraded:
— Wire runs must not exceed 250 feet.
— For distances up to 100 feet, typical twisted pair, PVC-insulated
shielded cable must be used.
— For distances from 100–150 feet, twisted pair shielded cable with
polypropylene insulated conductors must be used.
— For distances from 150–250 feet, twisted pair shielded cable with
foam-polyethylene insulated conductors must be used.
Rev. 01, 08/2011
Replaces S1B35793, 07/2011
DANGER
S1B35793

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Wiser EER57200

  • Página 3: Descripción

    Modelo EER57200 Conservar para uso futuro. Descripción El modelo EER57200 es un sensor de temperatura para montar en una superficie el cual ha sido diseñado para usarse con los termostatos programables Wiser con comunicación modelos EER56000 y EER56100. El sensor puede: estar conectado a un termostato Wiser para supervisar la temperatura de una ubicación remota...
  • Página 4: Configuración

    Calz. J. Rojo Gómez 1121-A Col. Gpe. del Moral 09300 México, D.F. Wiser™ y Schneider Electric™ son marcas comerciales o marcas registradas de Schneider Electric. Cualquier otra marca comercial utilizada en este documento Tel. 55-5804-5000 pertenece a sus respectivos propietarios.

Tabla de contenido