TruPortal Dual Door Interface Module
The Dual Door Interface Module TP-ADD-2D is capable of supporting two
complete door configurations, with up to two readers per door. This dual
door interface module provides termination points for door contacts (door
position switches) and request to exit devices as well as two door strike
relays to control power to the controlled access doors. It communicates to
the TruPortal family of system controllers (TP-SYS) via a 2-wire RS-485
bus.
The TruPortal Dual Door Interface Module is available in a board-only
configuration (TP-ADD-2D-BRD)
or CE enclosure with or without bundled readers and credentials
(TP-ADD-2DR, TP-ADD-2D).
Packing List
Dual Door Interface Module (quantity = 1)
Mounting plate (depending on option ordered)
UL or CE enclosure with power supply (depending on option ordered)
Installation kit which includes:
-
Two positional terminal plug-in block (quantity = 5)
-
Three positional terminal plug-in block (quantity = 4)
-
Four positional terminal plug-in block (quantity = 4)
-
Six positional terminal plug-in block (quantity = 2)
-
1N4005 diodes (quantity = 2)
-
End of line resistors 1k ohm, 1% (quantity = 8)
-
Plastic board supports for optional mounting (quantity = 4)
Model Numbers
The Dual Door Interface Module is available in the following
configurations:
TP-ADD-2D-BRD (board only)
TP-ADD-2D (installed in UL enclosure)
TP-ADD-2D2R (installed in UL enclosure and bundled with 2
readers)
TP-ADD-2D-E (installed in CE enclosure)
Note:
-E model numbers are "Not Evaluated by UL" and therefore
cannot be used in UL installations.
Mounting the Module
If you are adding a TP-ADD-2D-BRD to an existing enclosure (e.g., a
TP-ADD-2D with available space) use the provided screws as required to
mount the unit in one of the designated enclosures.
Determine the series of eight standoffs for mounting the module. Insert the
module and mounting plate assembly and attach it with the eight nuts
provided.
Note:
Do not over-tighten the mounting screws.
Anti-attack Bushing Cap
If this module is being mounted in the same enclosure as the TruPortal
System Controller, or added to an existing enclosure of another
TP-ADD-2D unit, an anti-attack bushing cap covers a rear tamper spring. It
fits inside an O ring bushing located in the cabinet's rear wall anti-tamper
spring knockout. Leave the O ring bushing and cap in place if the rear
tamper is not used.
TruPortal Dual Door Interface Quick Reference
TruPortal Dual Door Interface Module Quick Reference
(for TP-ADD-2D-BRD, TP-ADD-2D, TP-ADD-2D-E,
(See Figure 1.)
or pre-installed in a UL
TP-ADD-2D2R) en-US
If the rear tamper is used:
1.
Remove the cap and the O ring with the edge of a flat screwdriver.
2.
Discard the O ring.
3.
Align the cap for the tamper spring and knockout hole on the cabinet
back.
4.
Screw the cap into the mounting surface.
5.
Place the control cabinet over it, allowing the rear tamper spring to fit
inside the cap. The cap will fit into the cabinet's tamper spring
knockout hole.
6.
Secure the cabinet to the mounting surface.
Wiring
(See Figure 2.)
Door Unlock Circuit: A diode is provided to protect against voltages
induced when a DC strike is de-energized. For an AC strike, or a magnetic-
lock with reversing coils (or if unsure), you must use a 27 V Metal Oxide
Varistor (MOV).
Verify that at least 10.5 VDC is at each device (with relays energized). Use
additional power supplies as necessary.
For large current-draw devices with built-in power supplies, connect the
incoming and outgoing module bus +12 VDC lines together, but do not
connect to the +12 VDC in the cabinet.
Output Wiring
The contact protection circuit must be used. The following two circuits are
recommended. Locate the protection circuit as close to the load as possible
(within 12 inches [30 cm]), as the effectiveness of the circuit will decrease if
it is located further away.
1 (NC)
2 (C)
3 (NO)
Callout
Description
1
12 VDC
2
DC strike
1
1
+
-
3
Callout
Description
3
Diode current rating
>1x strike current.
Diode breakdown
voltage >4x strike
voltage for 12 or 24
VDC strike. Diode
1N4002 (100 V/1 A)
typical.
P/N 460802991B 26JAN12 en-US
2
-
+

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Interlogix TruPortal TP-ADD-2D Serie

  • Página 7: Módulo De Interfaz Dual Para Puertas Truportal

    Consulta rápida del módulo de interfaz dual para puertas TruPortal (para TP-ADD-2D-BRD, TP-ADD-2D, TP-ADD-2D-E, TP-ADD-2D2R) es-ES Módulo de interfaz dual para puertas antisabotaje de la pared posterior del gabinete. Si no se usa el dispositivo antisabotaje posterior, dejar en su lugar el pasante de junta tórica y la tapa. TruPortal Si se usa el dispositivo antisabotaje posterior: El módulo de interfaz dual para puertas TP-ADD-2D tiene capacidad para la...
  • Página 8: Cableado De La Lectora

    Cableado de la lectora Leyenda Descripción Leyenda Descripción 12 VCC Intensidad nominal TB11 del diodo >1 x intensidad de la RED/ cerradura. Tensión 5/12 GRN R1D1 R1D0 R2D1 R2D0 disruptiva del diodo >4 x tensión de la cerradura, para cerraduras de 12 o 24 VCC.
  • Página 9: Detalle Del Contacto De La Puerta Y Solicitud De Salida

    Leyenda Descripción Leyenda Descripción Detalle del contacto de la puerta y solicitud de salida Lectora Valor 0 de R2 (+) 5/12 VCC Rojo (1) LED verde Marrón (4) LED rojo Naranja (5) Valor 1 de R1 Blanco (3) 1 kΩ 1 kΩ...
  • Página 10: Especificaciones

    Especificaciones El TP-ADD-2D debe ser usado solo en circuitos clase 2 a baja tensión. Estas especificaciones están sujetas a cambios sin previo aviso. • Alimentación nominal de entrada: 12 VCC, 300 mA máx. • Salidas Cuatro salidas: Tipo de relé Cerradura: 24 VCC/1 A Aux.: 24 VCC/0,1 A •...
  • Página 11 Figura 1. Módulo de interfaz dual para puertas +12V +12V GND RTMP BUZ 5/12 GRN RED/ COM1 COM2 DCNT R1D1 R1D0 R2D1 R2D0 Descripción y propósito de cada clavija del módulo de interfaz dual para puertas Leyenda Descripción Leyenda Descripción Regleta Etiqueta de la Descripción...
  • Página 12 Regleta Etiqueta de la Descripción Regleta Etiqueta de la Descripción clavija clavija DCNT Entrada del contacto de TB11 5/12 (+) 5/12 VCC puerta LED verde Comunicación/ RED/RXD LED rojo compartida R1D1 Valor 1 de R1 RTMP Antisabotaje de la lectora R1D0 Valor 0 de R1 BUZ desactivado (-)
  • Página 13 Figura 2. Especificaciones de cables y componentes Leyenda Descripción Leyenda Descripción Leyenda Descripción Leyenda Descripción Cableado de la Alimentación de entrada auxiliar entrada 12 VCC Cable de lectora Puerta 1 o 2 (con (22 AWG, 1 par) (22 AWG, cierre de puerta) apantallado, 3 Entrada auxiliar Módulo de interfaz...
  • Página 14 Consulta rápida de la interfaz dual para puertas TruPortal P/N 460802991B 26ENE12 es-ES...
  • Página 22 Guide de référence rapide de l'interface double porte TruPortal P/N 460802991B 26JAN12 fr-FR...

Tabla de contenido