Descargar Imprimir esta página
Honeywell Fire-Lite BG-12L Manual

Honeywell Fire-Lite BG-12L Manual

Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

BG-12L Manual Pull Station
Patented, U.S. Patent No. Des. 428,351; 6,380,846; Other Patents Pending
Document 50964
Description
The BG-12L pull station is a non-coded, dual-action manual pull station with a key-lock
reset feature. It provides Fire•Lite control panels with one normally open (N/O) alarm initi-
ating input. The BG-12L meets the ADAAG controls and operating mechanisms guidelines
(section 4.1.3[13]), and the ADA requirement for a 5 lb. maximum pull force to activate
the pull station. Operating instructions are molded into the pull station handle along with
Braille text. Molded Terminal numbers are also present.
Ratings
Switch contact (N/O) is gold plated for reliability and rated at 0.25 A at 30 volts (AC or
DC).
Installation
The BG-12L pull station can be surface mounted to an SB-10 or SB-I/O surface backbox
or semi-flush mounted on a standard single-gang, double-gang or 4" (10.16 cm) square
electrical box. The optional BG-TR trim ring can be used if the BG-12L is to be semi-flush
mounted.
Operation
To activate the dual-action pull station, push in and pull down on the handle. The word
'ACTIVATED' appears after the handle is pulled down. This will remain until the pull sta-
tion is reset.
The pull station includes one Single Pole, Single Throw (SPST) Normally Open (N/O)
switch which closes upon activation of the pull station.
Resetting the Pull Station
1. Insert the key into the lock and rotate 1/4 turn counterclockwise.
2. Open the door until the handle returns to normal.
3. Close and lock the door.
Note: Closing the door automatically resets the switch to the 'Normal' position. Opening
the door will not activate or deactivate the alarm switch.
Wiring
FROM
FACP +
IDC –
1
STRIP GAUGE
I56-2263-004
WARNING: DO NOT LOOP WIRING
UNDER ANY TERMINALS. BREAK WIRE
RUN TO MAINTAIN IDC SUPERVISION.
WARNING! Do not loop wiring under any
terminals. Break wire run to
maintain IDC supervision.
CAUTION! Do not detach the door of the pull station during installation. The door of
the pull station cannot be reattached to the backplate after the backplate has already been
installed onto an electrical box.
CAUTION!
Install the Fire•Lite BG-12L pull station in accordance with these instructions,
applicable NFPA standards, national and local Fire and Electrical codes and the requirements
of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be con-
ducted in accordance with the appropriate NFPA standards. Failure to follow these directions
may result in failure of the device to report an alarm condition. Fire•Lite is not responsible for
devices that have been improperly installed, tested or maintained.
ADA Compliance
For ADA compliance, if the clear floor space only allows forward approach to an object, the
maximum forward reach height allowed is 48 inches (121.92 cm). If the clear floor space
allows parallel approach by a person in a wheelchair, the maximum side reach allowed is
54 inches (137.16 cm).
TO NEXT
+
DEVICE
Document 50964
– IDC
2
3
4
BG-12L
Manual Pull Station
I56-2263-004

Publicidad

loading

Resumen de contenidos para Honeywell Fire-Lite BG-12L

  • Página 1 Wiring BG-12L Manual Pull Station FROM TO NEXT FACP + DEVICE Document 50964 I56-2263-004 IDC – – IDC BG-12L Manual Pull Station Patented, U.S. Patent No. Des. 428,351; 6,380,846; Other Patents Pending STRIP GAUGE Document 50964 I56-2263-004 Description The BG-12L pull station is a non-coded, dual-action manual pull station with a key-lock reset feature.
  • Página 2 PRECAUCIÓN la manija haya sido tirada hacia abajo. Esta permanecerá hasta que la estación pulsadora Instale la estación pulsadora del Fire-Lite BG-12L de acuerdo con estas instrucciones, aplicando las sea reajustada. normas de la NFPA y los códigos y requisitos de fuego locales y nacionales de la AHJ ( Autoridad teniendo la juridicción).