The Photohelic
®
Switch/Gage is a very versatile, precise pressure
switch combined with the time-proven Magnehelic
Models are available with one or two phototransistor actuated relays.
Gage reading is unaffected by switch operation. Easy to adjust set points
have knob controls. Applied pressure and switch set points are fully
visible at all times. Deadband is one pointer width - less than 1% of full
scale. Double-pole double-throw relays can be easily interlocked to
provide variable deadband control. For positive, negative or differential
pressure only on 3600S models. Full scale ranges available from 0-.25
in w.c. to 0-6000 psig.
PHOTOHELIC
®
GAGE SENSING - HOW IT WORKS
In a typical control application, the Photohelic
between high and low pressure set points. When pressure changes,
reaching either set point pressure, the beam from an LED to the limiting
phototransistor will be cut off by the helix-driven light shield. The
resulting signal change is electronically amplified to actuate its DPDT
slave relay and switching occurs. Dead band between make and break
is 1% of full scale or less - just enough to assure positive, chatter-free
operation.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.
Series 3000 Photohelic
Specifications - Installation and Operating Instructions
1/8 FEMALE NPT HIGH
PRESSURE CONNECTION
1/8 FEMALE NPT LOW
PRESSURE CONNECTION
®
pressure gage.
®
switch/gage controls
Phone: 219/879-8000
Fax: 219/872-9057
®
Pressure Switch/Gage
2-1/2 [63.50]
2-1/16 [52.39]
2 [50.80]
Ø4-3/4
[120.65]
3-7/8 SQ
[98.43]
3/4 CONDUIT
CONNECTION
3-7/8 [98.43]
5-1/8 [130.18]
6-3/8 [161.93]
4-3/8 [111.13]
(7-5/8 [193.68])
HOUSING REMOVAL
Fig. 1
SPECIFICATIONS
GAGE SPECIFICATIONS
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Accuracy: ±2% of full scale at 70°F (21.1°C). ±3% on -0 and ±4% on
-00 models.
Pressure Limits: -20˝ Hg. to 25 psig (-0.677 to 1.72 bar). MP option;
35 psig (2.41 bar), HP option; 80 psig (5.52 bar). 36003S – 36010S;
150 psig (10.34 bar). 36020S and higher; 1.2 x full scale pressure.
Temperature Limits: 20 to 120°F (-6.67 to 48.9°C); Low temperature
option available.
Process Connections: 1/8˝ female NPT.
Size: 4˝ (101.6 mm) dial face, 5˝ (127 mm) O.D. x 8-1/4˝ (209.55 mm).
Weight: 4 lb (1.81 kg).
SWITCH SPECIFICATIONS
Switch Type: Each setpoint has 2 Form C relays (DPDT).
Repeatability: ±1% of full scale.
Electrical Rating: 10A @ 28 VDC, 10A @ 120, 240 VAC.
Electrical Connections: Screw terminals.
Power Requirements: 120 VAC, 50/60 Hz; 240 VAC & 24 VAC;
Power optional.
Mounting Orientation: Diaphragm in vertical position. Consult factory
for other position orientations.
Set Point Adjustment: Adjustable knobs on face.
www.dwyer-inst.com
e-mail: info@dwyer-inst.com
Bulletin B-33
(4) 6-32 HOLES
EQUALLY SPACED ON
A 5-1/8 [130.18] B.C.
1-1/4
[31.75]
Ø4-47/64
[120.25] Ø5
[127.00]
Ø4 [101.60]
FACE
5/8 [15.88]
5-1/2 [139.70]
5/8 [15.88] PANEL
O.D.
MAX
MOUNTING
3/16 [4.76]
RING

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Dwyer Instruments 3000 Serie

  • Página 7: Instrucciones Y Operacion

    Boletín B-33 El Interruptor/Indicador de Presión Photohelic ® Serie 3000 INSTRUCCIONES Y OPERACION 2-1/2 [63.50] (4) 6-32 HOLES 1/8 FEMALE NPT HIGH EQUALLY SPACED ON 2-1/16 [52.39] PRESSURE CONNECTION 2 [50.80] A 5-1/8 [130.18] B.C. 1-1/4 1/8 FEMALE NPT LOW PRESSURE CONNECTION [31.75] Ø4-3/4...
  • Página 8: Instalacion

    Boletín B-33 P. 2 INSTALACION Montaje: El Photohelic ® se monta normalmente antes de hacer las conexiones eléctricas, por lo tanto la carcasa eléctrica es independiente Localización: Todas las partes del interruptor/indicador Photohelic ® de la forma me montaje y puede ser quitada en cualquier momento. Dwyer ®...
  • Página 9 Boletín B-33 P. 3 Montaje del Indicador con los Relés Remotos: Donde se desee montar unidad relé-amplificador separada unidad indicador/fototransistor, el indicador puede montarse de cualquiera de las maneras mostra-das en la Fig. 2 (excepto la parte del relé- amplificador) o montarse sobre superficie como se muestra en la Fig 3A. Utilice el trazado monstrado en la Fig.
  • Página 10: Conexiones Electricas

    Boletín B-33 P. 4 CONEXIONES ELECTRICAS Los instrumentos de un Punto de Trabajo se suministran con los componentes del punto de trabajo de alta o derecho y la circuitería 1. Cubierta: La unidad relé-amplificador tiene una carcasa fácil de correspondiente. Esta está conectada a las Secciones A y B de la placa quitar.
  • Página 11 Boletín B-33 P. 5 6. Reset Manual de Doble Punto de Trabajo: El circuito tipo HH 8. Controlo del Límite Alta Baja-Doble Punto de Trabajo: El circuito también se puede utilizar para aplicaciones con reset manual donda se tipo HH puede usarse para controlar ventiladores, tiros, bombas, etc., desee hacer un contacto mantenido sobra cualquier relé...
  • Página 12: Mantenimiento Y Servicio

    3000-750Pa 0-750 25.0 0-1000 36100S 0-3000 36300S 0-6000 36600S ©Copyright 2010 Dwyer Instruments, Inc. Printed in U.S.A. 7/10 FR# 13-440202-02 Rev.5 DWYER INSTRUMENTS, INC. Phone: 219/879-8000 www.dwyer-inst.com P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com...

Este manual también es adecuado para:

Photohelic 3000-00Photohelic 3000-0Photohelic 3001Photohelic 3002Photohelic 3003Photohelic 3004 ... Mostrar todo

Tabla de contenido