INSTALLATION AND MAINTENANCE INSTRUCTIONS
SC-6
Six Supervised Control Module
SPECIFICATIONS
Normal Operating Voltage:
Stand-By Current:
Alarm Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
Wire Gauge:
Maximum Monitored Output Circuit
Wiring Resistance:
Table 1:
CURRENT RATING
3A
2A
1A
.5A
BEFORE INSTALLING
This information is included as a quick reference installation
guide. Refer to the appropriate control panel installation manual
for detailed system information. If the modules will be installed
in an existing operational system, inform the operator and local
authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the
modules. This system contains static sensitive components.
Always ground yourself with a proper wrist strap before handling
any circuits so that static charges are removed from the body. The
housing cabinet should be metallic and suitably grounded.
NOTICE: This manual should be left with the owner/user
of this equipment.
GENERAL DESCRIPTION
The SC-6 Six Supervised Control Module is intended for use in an
intelligent alarm system. Each module is intended for switching
applications involving DC which require wiring supervision. A
common SLC input is used for all modules. Each module has its
own address. A pair of rotary code switches is used to set the
address of the first module from 01 to 94. The remaining mod-
ules are automatically assigned to the next five higher addresses.
Provisions are included for disabling a maximum of three unused
modules to release the addresses to be used elsewhere. Each
module also has panel controlled green LED indicators. The panel
can cause the LEDs to blink, latch on, or latch off.
Each module has terminals for connection to an external supply
circuit for powering devices on its Monitored Output Circuit.
Each supply must be power limited and its voltage/current limits
must be at or below those specified in Table 1.
There is a short circuit protection monitor for each module. This
is provided to protect the external power supply against short
circuit conditions on the Monitored Output Circuit.
D500-68-00
15-32VDC
2.25 mA
35 mA (assumes all six relays have been switched once and all six LEDs solid on)
-10°C to 55°C
10 to 93% Non condensing
17.3cm H x 14.7cm W x 3.2cm D
Suitably grounded metallic cabinet
0.9mm 2 - 3.25mm 2
40 Ohms
MAXIMUM VOLTAGE
30VDC
30VDC
30VDC
30VDC
Included:
(7) 1 x 4 Terminal
(2) Screws
(1) Long Power
Supply Jumper
Shipped on Board:
(1) Small shunt
(6) Large shunts on Enable Power Supply Monitors
(6) Large shunts on Disable Short Circuit Protection
(3) Large shunts on Sync Generator
NOTE: Three shunts on Sync Generator MUST NOT be removed.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a
listed compatible control panel.
The SC-6 Module shall be mounted in a suitably grounded
Metallic Cabinet for EMC compliance.
1
LOAD DESCRIPTION
Resistive
Resistive
Inductive (L/R=2ms)
Inductive (L/R=5ms)
(2) 32mm Stand offs
Blocks
(5) Short Power
Supply Jumpers
(2) EOL Relay
Pittway Technologica S.p.A
Via Caboto 19/3
34147 Trieste, Italy
APPLICATION
Steady
Pulsing
Pulsing
Pulsing
(15) Large
Shunts
(2) Small Shunts
(6) 47k Ohm
End of Line
Resistors
Connector Assembly
I56-2253-01

Publicidad

loading

Resumen de contenidos para System Sensor SC-6

  • Página 9: Módulo De Control Con 6 Circuitos De Salida Supervisada

    (1) Puente de DESCRIPCIÓN GENERAL alimentación largo (6) Resistencia El Módulo de Control SC-6 ha sido diseñado para su uso en un de fin de línea sistema de alarma inteligente. Cada módulo sirve para conectar de 47k Ohmios aplicaciones que tengan corriente continua (DC) y que requieran supervisión del cableado.
  • Página 10 NOTA: Guarde los puentes no utilizados para un posible uso en el correspondientes. futuro. 2. Todo el cableado del SC-6 se efectúa mediante bloques de NOTA: El cableado de lazo SLC es el bloque de terminales superior, terminales. Efectúe las conexiones eléctricas pelando unos el circuito de señalización/alimentación es el inferior para el...
  • Página 11 Los CIRCUITOS DE SALIDA SUPERVISADOS se pueden conectar por Se puede conectar una única fuente de alimentación de modo que medio de fuentes externas individuales (las figuras 2 son un ejem- pueda ser compartida por varias placas PCB situadas en la misma plo), o varios circuitos de señalización pueden compartir una única cabina (la figura 4 es un ejemplo).
  • Página 12: Fuente De Alimentación Externa

    – PCB 1 PCB 2 FUENTE DE ALIMENTACIÓN EXTERNA VISTA A-A Figura 4: Ejemplo de varios tarjetas que comparten la misma fuente externa de alimentación. La alimentación la comparten los CIRCUITOS DE SALIDA SUPERVISADOS +0 y +1 (de la PCB 1) así como los +3, +4 y +5 (de la PCB 2). Consulte las figuras 3 para ver un ejemplo de cableado típico del CIRCUITO DE SALIDA SUPERVISADO.