Lista de los códigos de error del variador de velocidad
NOTA: el código 6 corresponde a un defecto de la sonda térmica y el código 33 corresponde
a motor no conectado
N°
Code
1
rES
Spare
DC bus voltage has
exceeded the peak level or
2
OV
maximum continuous level for
15 seconds
Instantaneous output over
3
OI.AC
current detected
Braking IGBT over current
detected: short circuit pro-
4
OI.br
tection for the braking IGBT
activated
5
PSU
Internal power supply fault
6
Et
An External trip is initiated
Motor frequency has
7
O.SPd
exceeded the over fre-
quency threshold
8
U.OI
User OI ac
9
rES
Spare
Brake resistor over tempera-
10
th.br
ture
11-12
rES
Spare
Measured inertia has
13
tunE
exceeded the parameter
range
14-17
rES
Spare
Autotune test stopped before
18
tunS
completion
Braking resistor overload
19
It.br
timed out (I2t)
Output current overload
20
It.aC
timed out (I2t)
Indice de revisión : E - Julio de 2017
State
• Increase deceleration ramp
• Check motor insulation using a insulation tester
• Increase acceleration/deceleration rate
• Check for short circuit on the output cabling
• Check integrity of the motor insulation using an
insulation tester
over current has been detected in braking IGBT or
braking IGBT protection has been activated
There is a hardware fault within the drive – return
the drive to the supplier
• Check motor temperature
• Check the thermal sensor.
Check that a mechanical load is not driving motor
the output current of the drive exceeds the trip
level
• Check brake resistor wiring
• Check braking resistor value is greater than or
equal to the minimum resistance value
• Check braking resistor insulation
The drive has tripped during a rotating autotune or
mechanical load measurement test.
Check motor cable wiring is correct
The drive was prevented from completing an
autotune test, because either the drive enable or
the drive run were removed.
Check the drive enable signal (Terminal 11) was
active during the autotune
• Ensure the load is not jammed / sticking
• Check the load on the motor has not changed
• Tune the motor rated speed parameter (Pr 5.008)
(RFC-A mode only)
• Ensure the motor rated current is not zero
41
Possible Cause and recommended action
6424