Idiomas disponibles
  • ES

Idiomas disponibles

Enlaces rápidos

PM84x Series 13.8 V DC Switch Mode Power
Supplies Installation Sheet
EN DE ES FR
IT
EN: Installation Sheet
Features
High efficiency cost effective power supply ideal for use in
Intruder, Access Control and General Security applications.
Featuring a regulated 13.8 V DC output supplying continuous
full rated current to load plus additional current for charging a
standby battery. Maximum battery life is assured using deep
discharge protection to prevent premature battery failure when
operating in standby mode for extended periods*. Two sets of
volt-free contacts are provided to signal (i) loss of mains and
(ii) battery and loss of output faults*.The universal mains input
voltage enables the power supply to be used across a wide
geographical area. The highly efficient switch mode design
ensures low operating costs, generates less heat and with a
small physical size increases the room available for additional
PCBs or cables. The modular construction simplifies
maintenance.
Continuous full rated current to load
Additional current to charge a standby battery
Battery Deep Discharge Protection*
Universal mains input voltage 90-264 V AC
Volt free contact signaling mains failure*
Volt free contact signaling output and battery faults*
High efficiency electronics for reduced running costs and
lower operating temperatures
Installer safe design with all high voltage electronics fully
shrouded
Modular construction for ease of maintenance and
installation
Full electronic short circuit and overload protection on load
output under mains operation
Mains transient protection circuit
Lid opening tamper detection
Removal from mounting tamper detection*
Green Mains present LED
Red Fault LED
* Dependent on model
© 2020 Carrier. All rights reserved. Specifications subject to change without prior notice
Installation instructions
This unit is only suitable for installation as permanently
connected equipment. The PSU is NOT SUITABLE for external
installation. EQUIPMENT MUST BE EARTHED. Before
installation, ensure that external disconnect device is OFF. The
PSU should be installed according to all relevant safety
regulations applicable to the application.
PM841, PM842 and PM844-A layout
100mm (min) all around
Fig 1. Location diagram
Mounting
1.
Mount securely in correct orientation allowing the
minimum clearance – see diagram.
2.
Route mains and low voltage output cables via different
knockouts and/or cable entry holes.
3.
Use bushes and cable glands rated to UL94 HB minimum.
Mains power-up
1.
Attach correctly rated mains cable (minimum
0.5 mm
2
[3 A], 300/500 V AC) and fasten using cable ties.
2.
Apply mains power. Check for 13.8 V DC on load outputs.
Check green Mains LED is on.
3.
Disconnect mains power.
Load output
1.
Attach correctly rated load cable and fasten using cable
ties. Note polarity.
2.
Apply mains power. Check green Mains LED is on.
Note:
Red LED may flash or be steady on (dependent upon
model) to indicate that no battery has been connected. This is
normal.
P/N PAK200503 REV 04A • ISS JUN 21
Tabla de contenido
loading

Resumen de contenidos para Aritech PM84 Serie

  • Página 7: Es: Hoja De Instalación

    instalar de acuerdo con todos los reglamentos de seguridad ES: Hoja de instalación pertinentes que procedan para la aplicación. Diseño de la PM841, PM842 & PM844-A Características Fuente de alimentación rentable y de alto rendimiento ideal 100 mm alrededor para su uso en control de intrusos y de acceso y aplicaciones generales de seguridad.
  • Página 8: Manipulación

    Instrucciones de funcionamiento †Compruebe que los contactos de Fallo EPS y GEN estén CERRADOS Esta unidad está pensada para ser utilizada exclusivamente Desconecte la red eléctrica. Compruebe que la batería por el personal de servicio. NO contiene piezas que requieran sigue suministrando tensión e intensidad a la carga.
  • Página 9: Conexiones

    Fusible de carga de 1 x BS127N 1 x BS131N Capacidad de la batería F4,0 A la batería (7,2 Ah) (18 Ah) Peso (kg) sin incluir la Valor nominal de 0,05 A, 24 V 0,05 A, 24 V 3 A, 125 V batería manipulación Datos medioambientales...

Este manual también es adecuado para:

Pm841Pm842Pm844-a

Tabla de contenido